| FCC 1000W - Single Zone Fire Alarm Controls |
|
|
Features:
Monitored detector zone for use with smoke detectors, heat detectors and manual call points
Two fused sounder circuits, monitored for open and short circuits
Mutable fault monitoring for mains, power supply unit, battery, sounders and detectors
500 mA power supply unit, with space for up to 4.2 A.H. sealed lead acid batteries
High brightness dual LED indicators
Touch sensitive controls
This single zone control has been designed to conform with the requirements of BS 3116 and BS 5839
|
For ease of installation and service, connections are made to a small rear mounted printed circuit board that also holds the battery and sounder fuses. The metal case has three point key-slot fixing with 20 mm conduit trunking top and bottom entry points
The detection zone is monitored with an end of line resistor to give fault and fire indications. They will monitor upto 35 low current smoke detectors and an infinite number of manual call points or other OC devices
The sounder circuits are fused and monitored for open and short circuits with an end of line resistor. Upto 20 low current sounders (25 mA) may be fitted
The power supply is fully monitored for failure, mains failure, battery failure, low voltage and battery disconnection
The user controls are enabled by means of a security keyswitch
Mute Sounders - mutes sounders and fault warning
Sound Alarm - to evacuate building or resound alarm
Reset (Test) - to reset control and detectors and test control
Indications are provided for mains power, zone fire, zone fault, sounder fault and power fault
Audible indications are provided for fire and fault
Printed circuit boards are available as new for spares
|
|
|
| FCC 2000W - Two Zone Fire Alarm Controls |
|
|
Features:
Monitored detector zones for use with smoke detectors, heat detectors and manual call points
Two fused sounder circuits, monitored for open and short circuits
Mutable fault monitoring for mains, power supply unit, battery, sounders and detectors
1 amp power supply unit, with space for up to 6 A.H. sealed lead acid batteries
5 amp alarm relay output and 24 volt DC output
High brightness dual LED indicators and touch sensitive controls
This dual zone control has been designed to conform with the requirements of BS 3116 and BS 5839
|
For ease of installation and service, connections are made to a small rear mounted printed circuit board which also holds the battery and sounder fuses. The metal case has three point key-slot fixing with 20 mm conduit trunking top and bottom entry points
The detection zones are monitored with an end of line resistor to give fault and fire indications. They will monitor upto 35 low current smoke detectors and an infinite number of manual call points or other OC devices
The sounder circuits are fused and monitored for open and short circuits with an end of line resistor. Upto 40 low current sounders (25 mA) may be fitted
A voltage free 5 A relay is provided for door closers, signaling etc
A monitored fused 24 V D.C. output is provided
The power supply is fully monitored for failure, mains failure, battery failure, low voltage and battery disconnection
The user controls are enabled by means of a security key-switch
Mute Sounders - mutes sounders and fault warning
Sound Alarm - to evacuate building or resound alarm
Reset (Test) - to reset control and detectors and test control
Indications are provided for mains power, common fire, zone fire, common fault, zone fault, sounder fault and power fault
Audible indications are provided for fire and fault
Printed circuit boards are available as new for spares
|
|
|
| FCC 3000W - Multi Zone Fire Alarm Controls |
|
|
Features:
This control panel has been designed for the professional installer to conform with the requirements of BS 3116 and BS 5839, 1988
The master control unit can have from one to four zones extendable internally using plug in zone cards. The master control may be extended with 10-zone extender units and plug in zone cards
The modular system allows minimum stocking requirements, ease of service and maintenance, ease of system extension and future system upgrades
Plug in Bell delay modules
Non Latch test facility
Fire and Auxiliary relay outputs
Zone isolation
|
Add on gas extinguishing control units are available to extend the system or an area within the system to a double knock automatic gas release system
Outputs for repeater panels, communicators, door closers extractors etc
The detection zones are monitored with an end of line resistor to give fault and fire indications. They will monitor up to 35 low current smoke detectors and an infinite number of manual call points or other Open Circuit devices
The sounder circuits are fused and monitored for open and short circuits with an end of line resistor. Up to 40 low current sounders (25 mA) may be fitted
The power supply is fully monitored for failure, mains failure, battery failure, low voltage and battery disconnection
The user controls are enabled by means of a security keys-witch
Mute Sounders - mutes sounders and fault warning
Sound Alarm - to evacuate building or resound alarm
Reset (Test) - to reset control and detectors and test control
Indications are provided for mains power, common fire, zone fire, common fault, zone fault, sounder fault and power fault
Audible indications are provided for fire and fault
Printed circuit boards are available as new for spares
|
|
| |
|
|